Your Rental Location
  • Request A Quote

Emergency Transfer Load manager

The EXL is a wall mounted system that monitors and controls a single engine generator for operation in parallel with a single utility source. The EXL will support Emergency Standby as well as Utility Paralleling applications.

Videos not available for this product.

360 View not available for this product.

SPECIFICATION SUMMARY
  • Configuration Wall mounted paralleling control system that monitors and controls a single generator and a single utility.
  • Modes of Operation Utility Import, Export, and base load operations, Peak shaving, and Emergency Standby. Closed Transition to/from Generator Power
  • Application LV and MV (208V-32kV)
  • Operating Temperature 0-50°C

PRICE (USD)
Call 440-838-7348 for rate information

Technical Summary

  • Configuration
    Wall mounted paralleling control system that monitors and controls a single generator and a single utility.
  • Modes of Operation
    Utility Import, Export, and base load operations, Peak shaving, and Emergency Standby. Closed Transition to/from Generator Power
  • Application
    LV and MV (208V-32kV)
  • Configuration
    Wall mounted paralleling control system that monitors and controls a single generator and a single utility.
  • Modes of Operation
    Utility Import, Export, and base load operations, Peak shaving, and Emergency Standby. Closed Transition to/from Generator Power
  • Application
    LV and MV (208V-32kV)

Environmental Parameters

  • Operating Temperature
    0-50°C
  • Storage Temperature
    -20°C to +60°C
  • Medium Voltage Standards
    NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
  • Certifications
    IBC, CBC, UBC, & OSHPD Certified
  • Control Panel Enclosure
    NEMA 1 or NEMA 3R Freestanding Construction
  • Low Voltage Standards
    NEMA SG-5, CSA,ANSI C37.51, ANSI C37.20.1, UL1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
  • Operating Temperature
    0-50°C
  • Storage Temperature
    -20°C to +60°C
  • Medium Voltage Standards
    NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110

Generator Protective Devices

  • ANSI Protective Devices
    15/25. 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

  • ANSI Protective Devices
    15/25. 27/59, 81 O/U, 32, 40, 47, 51, 86

Product Features

  • Automatic Synchronizing and Paralleling Controls
  • Automatic operation Emergency Standby applications
  • Communications with the on package genset controller which affords viewing of detailed engine and generator parameters on the LCD display
  • Accommodates interface to a user Building Management System via ModBus RS-485
  • User configurable engine exercise mode
  • Password Security System to ensure system security

Standard Equipment:

  • Instant Auto Selector Switch
    • Allows user to return sysem to automatic in the event of a touchscreen failure
  • Spare Inputs And Outputs
    • 3 digital inputs and 6 relay outputs programmable from the HMI

Optional Equipment:

  • Supplemental Hardware 25 Device
    • Provides additional discrete synchronization protection