The Emergency Transfer and Load management (XLM) product supports transfer between the utility source and generator bus and allows for sustained parallel operation with the utility for load management applications.

Videos not available for this product.

360 View not available for this product.

SPECIFICATION SUMMARY
  • Configuration Traditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
  • Modes of Operation Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
  • Application LV and MV ( 208V - 38 kV
  • Operating Temperature 0 degrees to 50 degrees C

PRICE (USD)
Call 440-838-7348 for rate information

Technical Summary

  • Configuration
    Traditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
  • Modes of Operation
    Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
  • Application
    LV and MV ( 208V - 38 kV
  • Configuration
    Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
  • Modes of Operation
    Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
  • Application
    LV and MV ( 208V - 38 kV

Environmental Parameters

  • Operating Temperature
    0 degrees to 50 degrees C
  • Storage Temperature
    -20 degrees C to +60 degrees C
  • Medium Voltage Standards
    NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
  • Certifications
    IBS, CBC, UBC & OSHPD Certified
  • Control Panel Enclosure
    NEMA 1 or NEMA 3R, Freestanding Construction
  • Low Voltage Standards
    NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
  • Operating Temperature
    0 degrees to 50 degrees C
  • Storage Temperature
    -20 degrees C to +60 degrees C
  • Medium Voltage Standards
    NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110

Generator Protective Devices

  • ANSI Protective Devices
    15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

  • ANSI Protective Devices
    15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86

XLM Switchgear

  • High Speed Supervisory Network
  • Automatic Start/Stop
  • Automatic “Dead Bus” Coordination
  • Automatic Power Factor Control when in Parallel with Utility Power
  • Programmable Load Shed / Load Add Functions
  • Networked Engine Communications
  • Generator & Utility Protection
  • Engine Tuning
  • Mode Selection
  • Selectable Auto/ Manual Control
  • Password Protection for Protective Settings and Setup
  • Load/No Load Test
  • Touch Screen (HMI) Display
  • NFPA 99/110 Compliant Alarm
  • Annunciation with Audible Horn
  • Engine Control mimic Screen with gauges for RPM, DC Battery Voltage, Oil Pressure, Engine Coolant temperature, Engine Hours, Number of starts

Standard Equipment:

  • Generator Demand Priority Control
    • Automatically match the on-line generator capacity to the loads, and avoid unnecessary operation of generator sets.

Optional Equipment:

  • Data Table Interface
    • Accommodates interface with a building management system for monitoring all system parameters via Modbus RTU or TCP
  • Supplemental Hardware Synchronization Check Relay (ansi 25 Device)
    • Provides additional discrete synchronization protection
  • Remote Power Monitoring System
    • To monitor breaker status, alarms, metering and other operating parameters