Cat EGP Switchgear

EGP (Emergency Generator Paralleling) switchgear is used for paralleling multiple generators that are not directly connected to a utility source.

Videos not available for this product.

360 View not available for this product.

SPECIFICATION SUMMARY
  • Configuration Traditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
  • Modes of Operation Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
  • Application LV and MV (208V - 38 kV)
  • Operating Temperature 0°C to 50°C

PRICE (USD)
Call 440-838-7348 for rate information

Technical Summary

  • Configuration
    Traditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
  • Modes of Operation
    Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
  • Application
    LV and MV (208V - 38 kV)
  • Configuration
    Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications
  • Modes of Operation
    Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
  • Application
    LV and MV (208V - 38 kV)

Environmental Parameters

  • Operating Temperature
    0°C to 50°C
  • Storage Temperature
    -20°C to +60°C
  • Medium Voltage Standards
    NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
  • Certifications
    IBC, CBC, UBC & OSHPD Certified
  • Control Panel Enclosure
    NEMA 1 or NEMA 3R Freestanding Construction
  • Low Voltage Standards
    NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
  • Operating Temperature
    0°C to 50°C
  • Storage Temperature
    -20°C to +60°C
  • Medium Voltage Standards
    NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110

Generator Protective Devices

  • ANSI Protective Devices
    15/25, 27/59, 81 O/U, 32, 40, 50, 51

EGP Switchgear

  • High Speed Supervisory Network
  • Automatic Start/Stop
  • Automatic “Dead Bus” Coordination
  • Programmable Load Shed / Load Add Functions
  • Networked Engine Communications
  • Generator Protection
  • Engine Tuning
  • Mode Selection
  • Selectable Auto/ Manual Control
  • Password Protection for Protective Settings and Setup
  • Load/No Load Test
  • Touch Screen (HMI) Display
  • NFPA 99/110 Compliant Alarm
  • Annunciation with Audible Horn
  • Engine Control mimic Screen with gauges for RPM, DC Battery Voltage oil Pressure, Engine Coolant temperature, Engine Hours, Number of starts

Standard Equipment:

  • Egp Switchgear
    • Choice of 19” Surface Acoustic Wave Color or 15” Resistive Color Touchscreen
    • Emergency Stop Button for each generator
    • Instant Auto Switch
    • Generator Demand Priority Control
    • Audible Alarm & Horn Silence Button
    • Circuit Breaker Control Switch with Indicators

Optional Equipment:

  • Data Table Interface
    • * Accomodates interface with a building management system for monitoring all system parameters via Modbus RTU or TCP
  • Supplemental Hardware Synchronization Check Relay (ansi 25 Device)
    • * Provides additional discrete synchronization protection
  • Remote Power Monitoring System
    • * To monitor breaker status, alarms, metering and other operating parameters