Cat EGP Switchgear
The Cat® MMC-M is designed for large industrial/commercial installations. The MMC-M will integrate a variety of traditional and renewable energy sources to provide overall monitoring and control of the assets. These assets may be either located at a common installation or dispatched over a wider region.
Videos not available for this product.
360 View not available for this product.
SPECIFICATION SUMMARY
- Configuration Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications
- Modes of Operation Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
- Application LV and MV (208V - 38 kV)
- ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51
PRICE (USD)
Call 440-838-7348 for rate information
Technical Summary
-
ConfigurationConfigurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications
-
Modes of OperationMulti-unit Island and multi-unit standby mode with optional redundant controls and components.
-
ApplicationLV and MV (208V - 38 kV)
Generator Protective Devices
-
ANSI Protective Devices15/25, 27/59, 81 O/U, 32, 40, 50, 51
Environmental Parameters
-
CertificationsIBC, CBC, UBC & OSHPD Certified
-
Control Panel EnclosureNEMA 1 or NEMA 3R Freestanding Construction
-
Operating Temperature0°C to 50°C
-
Storage Temperature-20°C to +60°C
-
Low Voltage StandardsNEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
-
Medium Voltage StandardsNEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
EGP Switchgear
- High Speed Supervisory Network
- Automatic Start/Stop
- Automatic “Dead Bus” Coordination
- Programmable Load Shed / Load Add Functions
- Networked Engine Communications
- Generator Protection
- Engine Tuning
- Mode Selection
- Selectable Auto/ Manual Control
- Password Protection for Protective Settings and Setup
- Load/No Load Test
- Touch Screen (HMI) Display
- NFPA 99/110 Compliant Alarm
- Annunciation with Audible Horn
- Engine Control mimic Screen with gauges for RPM, DC Battery Voltage oil Pressure, Engine Coolant temperature, Engine Hours, Number of starts
Standard Equipment:
-
- Egp Switchgear
-
- Instant Auto Switch
- Emergency Stop Button for each generator
- Generator Demand Priority Control
- Circuit Breaker Control Switch with Indicators
- Audible Alarm & Horn Silence Button
- Choice of 19” Surface Acoustic Wave Color or 15” Resistive Color Touchscreen
Optional Equipment:
-
- Data Table Interface
-
- * Accomodates interface with a building management system for monitoring all system parameters via Modbus RTU or TCP
-
- Supplemental Hardware Synchronization Check Relay (ansi 25 Device)
-
- * Provides additional discrete synchronization protection
-
- Remote Power Monitoring System
-
- * To monitor breaker status, alarms, metering and other operating parameters