SPECIFICATION SUMMARY
- Aspiration Air to Air Aftercooled
- Fuel System Electronic unit injection
- Minimum Rating 550 kVA
- Maximum Rating 715 kVA
PRICE (USD)
Call 440-838-7348 for rate information
Engine Specifications
-
AspirationAir to Air Aftercooled
-
Fuel SystemElectronic unit injection
-
Engine ModelC18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
-
Bore145 mm (5.71 in)
-
Displacement18.13 L (1106.36 in3)
-
Stroke183 mm (7.2 in)
-
Compression Ratio14.5:1
-
Governor TypeAdemâ„¢A4
-
AspirationAir to Air Aftercooled
-
Fuel SystemElectronic unit injection
-
Displacement1106.36 in³
-
Fuel SystemElectronic unit injection
-
Stroke - HD
-
Bore5.71 in
-
Stroke7.2 in
Generator Set Specifications
-
Minimum Rating550 kVA
-
Maximum Rating715 kVA
-
Voltage380 to 415 Volts
-
Frequency50 Hz
-
Speed1500 rpm
-
Emissions/Fuel StrategyLow Fuel, China Nonroad III Emis Stds
-
Bore5.71 in
-
Stroke7.2 in
-
Duty CycleStandby, Prime
Generator Set Dimensions
-
Height - Maximum75 in
-
Length - Maximum162.4 in
-
Width - Maximum78.3 in
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
A-Frame Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
EMCP Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 55°C (131°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
World Wide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Standard Equipment:
-
- Air Inlet System
-
- Turbocharger
- Light duty air cleaner
- Aftercooler core
-
- Air Inlet
-
- Air Cleaner
-
- Control System
-
- EMCP 4.2
-
- Exhaust
-
- Exhaust flange outlet
-
- Cooling
-
- Coolant drain line with valve
- Caterpillar extended life coolant
- Fan drive, battery charging alternator drive
- Radiator and cooling fan with guard
-
- Exhaust System
-
- Stainless steel exhaust flex gaskets, raincap and SAE exhaust flange for customer use; shipped loose
-
- Fuel
-
- Secondary fuel filter
- Fuel priming pump
- Primary fuel filter with integral water separator
-
- Fuel System
-
- Standard 8 hour open set fuel tank
-
- Generator
-
- IP23 Protection
- Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
- Matched to the performance and output characteristics of Cat engines
-
- Generator And Attachments
-
- Segregated low voltage (AC/DC) wiring panel
- Integrated Voltage Regulator
- A frame generator - IP21 protection
- Integrated Voltage Regulator
- Mandatory Option circuit breaker, IEC, 3 pole, mounted in power centre
- Power center, IP22
- Matched to the performance and output characteristics of Cat engines
-
- Power Termination
-
- Bus Bar
-
- Governing System
-
- Cat Electronic Governor (ADEM A4)
-
- Control Panel
-
- EMCP 4 Genset Controller
-
- Lube System
-
- Lubricating oil
- Oil drain valves
-
- Mounting
-
- Rubber vibration isolators
-
- Mounting System
-
- Captive linear vibration isolators between base and engine-generator. includes lifting provisions and termination points for coolant and lube oil drain lines
-
- Starting/charging
-
- 24 Volt battery with rack and cables
-
- General
-
- Engine and alternator pre-paint, Caterpillar yellow
Optional Equipment:
-
- Exhaust
-
- Industrial, Residential, Critical Mufflers
-
- Air Inlet System
-
- Dual element air cleaner
- Single element air cleaner
-
- Circuit Breakers
-
- 3 Pole (IEC-100% rated) circuit breakers - Motorised
- 4 Pole (IEC-100% rated) circuit breakers - Motorised
- Circuit breaker (IEC) auxiliary contacts
- Pad-lockable circuit breaker device
- 3 Pole (IEC-100% rated) circuit breakers - Package mounted
- 4 Pole (IEC-100% rated) circuit breakers - Package mounted
- Power terminal strip
- Shunt trip for IEC breaker
-
- Generator
-
- Anti-condensation heater
- Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
- Oversize and premium generators
-
- Power Termination
-
- Circuit breakers, IEC compliant
- Circuit breakers, UL listed
-
- Control Panels
-
- Local & remote annunciator modules
- Load share module
- Remote monitoring software
- EMCP (4.2) (4.3) (4.4)
- Digital I/O module
-
- Control System
-
- Oil temperature displays
- EMCP 4.4
- Volt free contact
- Protective devices: Earth fault relay - earth leageage ground fault relay - Overload shutdown via breaker - Low fuel level alarm - Low fuel level shutdown - high fuel level alarm - Fuel level sensor
- Local alarm modules
- Remote annunciator modules
- Local alarm horn
-
- Cooling System
-
- Low coolant temperature alarm
- Radiator duct flange
-
- Starting/charging
-
- Oversize batteries
- Jacket water heater
- Battery chargers
- Heavy-duty starting system
- Charging alternator
-
- Enclosures
-
- Sound attenuated enclosures
-
- Exhaust System
-
- Manifold and Turbocharger guard
- Engine mounted muffler
- 8 and 10 inch elbow kits
- 8 and 10 inch GP flanges
- 10, 25 and 35 end in / end out Mufflers
-
- Fuel System
-
- Integral - Duel wall fuel tank base
- Manual fuel transfer pump
- Fuel transfer system
-
- Generator And Attachments
-
- LC frame generator
- Permanent magnet excitation
- LC frame oversize generators
- Space heaters
- A frame oversize generator
- A frame CIP generator
- Ingress protection
- LC frame CIP generator
-
- General
-
- Single or dual wall integral fuel tanks
- UL 2200 package
- Enclosures: sound attenuated, weather protective
- EU Certificate of Conformance (CE)
- Integral & sub-base UL listed dual wall fuel tanks
- Narrow, Wide or Skid Base
- The following options are based on regional and product configuration:
- Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
- EEC Declaration of Conformity
- CSA Certification
- Sound attenuated, weather protective or high ambient weather protective enclosure
- Automatic transfer switches (ATS)
- Single or dual wall sub-base fuel tanks
-
- Lube System
-
- Manual sump pump
-
- Starting And Charging
-
- Jacket water heaters
- 5 Amp battery charger
- Battery disconnect switch