Your Rental Location
  • Request A Quote

3512 with Flexible Packaging

The 3512A generator set with Flexible Packaging has been developed for a wide range of applications, from emergency standby installations such as healthcare and datacenters to continuously powering remote installations. The packages can be optimized for performance that matters to you with either low emissions or low fuel consumption versions available. Backed by the worldwide network of Cat dealers ready to support your operation with technical support, service, parts, and warranty, Cat generator sets will provide the reliability and durability you expect.

Videos not available for this product.

360 View not available for this product.

SPECIFICATION SUMMARY
  • Aspiration TA
  • Fuel System MEUI
  • Minimum Rating 1000 kVA
  • Maximum Rating 1400 kVA

PRICE (USD)
Call 440-838-7348 for rate information

Engine Specifications

  • Aspiration
    TA
  • Fuel System
    MEUI
  • Engine Model
    C32 TA, V-12, 4-Stroke Water-Cooled Diesel
  • Bore
    145 mm (5.71 in)
  • Stroke
    162 mm (6.38 in)
  • Displacement
    32.1 L (1958.86 in3)
  • Compression Ratio
    15.0:1
  • Governor Type
    Adem™A4
  • Exhaust Flange Size - Internal Diameter
    203.2 mm (8.0 in)
  • Air Inlet
    Single element canister style with service indicator
  • Aspiration
    TA
  • Fuel System
    MEUI
  • Air Inlet
    Single element canister style with service indicator
  • Displacement
    1958.9 in³
  • Bore
    5.71 in
  • Stroke
    6.38 in

Generator Set Specifications

  • Minimum Rating
    1000 kVA
  • Maximum Rating
    1400 kVA
  • Voltage
    220 to 13800
  • Frequency
    50 Hz
  • Speed
    1500 rpm
  • Emissions/Fuel Strategy
    Low fuel, Low Emissions

Generator Set Dimensions

  • Length - Maximum
    218.8 in
  • Height - Maximum
    93.2 in
  • Width - Maximum
    77.8 in

Cat Generator Set Package

Cat Diesel Engine

Generators

EMCP Control Panels

Cooling System

World Wide Product Support

Standard Equipment:

  • Air Inlet System
    • Air cleaner; single element canister type with service indicator
    • Air cleaner; single element canister type with service indicator
  • Control System
    • Controls:
    • Coolant temperature
    • Emergency stop
    • 2 programmable digital outputs
    • Generator phase sequence
    • Auto / Start / Stop control
    • Failure to start (overcrank)
    • Cat Connect
    • Engine cool-down timer
    • 4 programmable relay outputs (Form A)
    • kVAr-hr (total)
    • Reverse Power (kW) (32)
    • Serial annunciator module data link
    • 6 programmable digital inputs
    • Volts (L-L & L-N), frequency (Hz)
    • 2 programmable relay outputs (Form C)
    • Amps (per phase & average)
    • Accessory module data link
    • Oil pressure (psi, kPa or bar)
    • Engine cycle crank
    • kW (per phase, average & percent)
    • RPM
    • 24-volt DC operation
    • Overspeed
    • Generator mounted - rear facing
    • Low oil pressure
    • Operating hours
    • Emergency stop buttom
    • EMCP4
    • Power Factor (per phase & average)
    • DC volts
    • Environmental sealed front face
    • Over/Under Frequency (81 o/u)
    • Programmable protective relaying functions:
    • Communications:
    • Reverse Reactive Power (kVAr) (32RV)
    • Overcurrent (50/51)
    • Low coolant temperature
    • Over/Under voltage (27/59)
    • Low coolant level
    • Digital indication for:
    • Text alarm / event descriptions
    • kW-hr (total)
    • True RMS AC metering, 3-phase, +/-2% accuracy
    • Alarm acknowledge
    • Lamp test
    • Warning/shutdown with common LED indication of shutdowns for:
    • High coolant temperature
    • Customer data link (Modbus RTU)
  • Control Panel
    • Low oil pressure
    • 24-volt DC operation
    • Reverse Reactive Power (kVAr) (32RV)
    • True RMS AC metering, 3-phase, +/-2% accuracy
    • 4 programmable relay outputs (Form A)
    • Overcurrent (50/51)
    • Customer data link (Modbus RTU)
    • Low coolant temperature
    • Generator mounted - rear facing
    • Speed adjust
    • 2 programmable digital outputs
    • Power Factor (per phase & average)
    • Amps (per phase & average)
    • Failure to start (overcrank)
    • Generator phase sequence
    • Over/Under Frequency (81 o/u)
    • EMCP 4.2
    • Frequency (Hz)
    • Text alarm / event descriptions
    • Lamp test
    • kW-hr (total)
    • kVAr-hr (total)
    • 2 programmable relay outputs (Form C)
    • Volts (L-L & L-N)
    • Emergency stop pushbutton
    • 6 programmable digital inputs
    • Accessory module data link
    • High coolant temperature
    • Warning/shutdown with common LED indication of shutdowns for:
    • Communications:
    • Controls:
    • Alarm acknowledge
    • Emergency stop
    • Digital indication for:
    • Reverse Power (kW) (32)
    • Environmental sealed front face
    • Auto / start / stop control
    • DC volts
    • kVAr (per phase, average & percent)
    • Overspeed
    • Programmable protective relaying functions:
    • Engine cool-down timer
    • Coolant temperature
    • Oil pressure (psi, kPa or bar)
    • Serial annunciator module data link
    • kW (per phase, average & percent)
    • RPM
    • Engine cycle crank
    • kVA (per phase, average & percent)
    • Over/Under voltage (27/59)
    • Low coolant level
    • Operating hours
  • Cooling System
    • JWAC
    • Caterpillar extended life coolant. (Not included with packages without radiator, installed SF44CTS, shipped loose radiators or heat exchangers)
    • Coolant level sensors. (Not included with packages without radiator)
    • Coolant drain line with valve
    • Radiator fan and fan drive
    • Fan and belt guards.
    • Coolant level sensors (Not included with packages without radiator)
    • Coolant drain line with valve
    • Fan and belt guards
    • Caterpillar Extended Life Coolant (Not included with packages without radiator)
    • JWAC
    • Radiator fan and fan drive
  • Exhaust System
    • Dry Exhaust Manifold
    • Flanged faced outlet(s)
  • Exhaust
    • Dry Exhaust Manifold
    • Flanged faced outlet(s)
  • Fuel System
    • Fuel cooler; not included with packages without radiator
    • Secondary fuel filters
    • Fuel priming pump
    • Flexible fuel lines - shipped loose
    • Fuel cooler; not included with packages without radiator
    • Fuel priming pump
    • Secondary fuel filters
    • Flexible fuel lines - shipped loose
  • Generators And Attachments
    • Reactive droop capability
    • 3 Phase voltage sensing
    • 3 phase brushless, salient pole
    • LV:
    • Caterpillar's Digital Voltage Regulator (CDVR) includes:
    • KVAR/PF modes
    • Generator set packages include: Regulator (CDVR)
    • Random wound
    • 6 lead
    • Winding temperature detectors
    • Note: 1800 frames are form wound, permanent magnet, with winding temp detectors
    • Internal Excitation
    • RFI suppression
    • Min / max exciter limiter
    • 50 Hz models: IEC standard hole pattern
    • NEMA Class H insulation
    • Class H temperature rise at 40C ambient (125C prime/150C standby)
    • Exciter diode monitor
    • Busbar connections, top center mounted, top cable entry
  • Generator And Attachments
    • NEMA Class H insulation, Class H temperature rise at 40C ambient (125C prime/150C standby)
    • Random wound
    • Internal Excitation
    • Low Voltage:
    • 6 Lead
    • Bus bar connections, top center mounted, top cable entry
    • 1800 Frames are form wound, permanent magnet
    • Winding temperature detectors
    • 50 Hz models: IEC standard hole pattern
    • 3 Phase brushless, salient pole
    • Generator set packages include Caterpillar's Digital Voltage Regulator (CDVR) includes reactive droop capability, 3-phase voltage sensing KVAR/PF modes, RFI suppression, min/max exciter. Limiter and exciter diode monitor
  • Literature
    • English
  • Governing System
    • Woodward 2301A isochronous governor
    • Woodward 2301A isochronous governor
  • Lube System
    • Integral lube oil cooler
    • Oil filter, filler and dipstick
    • Gear type lube oil pump
    • Lubricating oil
    • Fumes disposal
    • Oil drain lines and valve
    • Oil drain lines and valve
    • Lubricating oil
    • Gear type lube oil pump
    • Integral lube oil cooler
    • Fumes disposal
    • Oil filter, filler and dipstick
  • Mounting System
    • Rails - engine/generator/radiator mounting
    • Rubber anti-vibration mounts (shipped loose)
    • Rubber anti-vibration mounts (shipped loose)
    • Rails - engine/generator/radiator mounting
  • Starting / Charging System
    • Battery disconnect switch
    • 24-volt electric starting motor
    • Battery and battery rack w/cables
    • SAE Standard Rotation
    • Right hand servicing
    • Flywheel and Flywheel housing-SAE No. 00
    • Caterpillar yellow with high gloss black rails and radiator paint
  • General
    • Flywheel and Flywheel housing-SAE No. 00
    • Paint - Caterpillar Yellow with high gloss black rails & radiator
    • SAE Standard Rotation
    • RH Service

Optional Equipment:

  • Air Inlet System
    • Air Inlet protection
    • Remote air inlet adaptors
    • Dual Element air cleaners
  • Circuit Breakers
    • Optional busbar power connections
    • EMAX circuit breakers
    • Controls packaging - Enclosures
    • EMAX breakers connections
    • Busbar connections
    • Breaker harnesses
    • Cable entry options
    • 2000, 2500, 3200 and 4000 Amp, 3 pole, IEC rated circuit breakers
    • Center posts busbars
    • 2000, 2500, 3200 and 4000 Amp, 4 pole, IEC rated circuit breakers
  • Engine Options
    • Battery Charger: [ ] 10A [ ] 20A [ ] 35A
    • Batteries: [ ] Standard (1400 CCA) [ ] Heavy Duty (2800 CCA)
    • Starting Motors: [ ] Standard [ ] Heavy Duty
    • Muffler: [ ] Industrial Grade
    • Starting Aids: [ ] 220V 50 Hz Jacket Water Heater
    • Air Cleaner: [ ] Single element air cleaners [ ] Dual element air cleaners [ ] Heavy duty air cleaners
  • Control Panels
    • Governors
  • Generators
    • Temperature Rise over 40°C ambient: [ ] 150°C [ ] 125°C [ ] 105°C [ ] 80°C
  • Power Termination
    • Power Termination: [ ] Bus Bar [ ] Circuit Breaker
    • Circuit Breaker rating: [ ] 2000A [ ] 2500A [ ] 3200A [ ] 4000A
    • Circuit breaker trip unit: [ ] LSI [ ] LSIG [ ] LSIG-P
  • Extended Service Contract
    • Extended Service Contract (ESC): [ ] 2 Year [ ] 3 Year [ ] 5 Year
  • Cooling System
    • Optional radiator arrangements
    • Water level switch gauges
    • Heat exchangers
  • European Certifications
    • European directive genset, DoI (Declaration of Incorporation)
    • European Union Certification
    • EU declaration of conformity
    • Eurasian conformity (EAC) mark
  • Exhaust System
    • Mufflers
    • Muffler mounting kits
    • Through-wall installation kit
    • Flexible fittings
  • Fuel System
    • Primary fuel filter
  • Generators And Attachments
    • 1500 RPM, 380/400/415volts @ 50 Hz, 3 phase, random wound, internal excitation, No. of leads = 6, pitch= 0.6667
    • Space heater
    • Generator conversion
    • 1500 RPM, 380/400/415volts @ 50 Hz, 3 phase, form wound, permanent magnet, No. of leads = 6, pitch= 0.6667
    • 1500 RPM, 380/400/415volts @ 50 Hz, 3 phase, random wound, permanent magnet, No. of leads = 6, pitch= 0.6667
  • Instrumentation
    • Pyrometer and thermocouples
  • Lube System
    • Oil level Reg-1 shallow pan
    • Electric prelube pumps
    • Manual prelube sump pumps
  • Mounting System
    • IBC vibration isolators
    • Spring-type vibration isolator
  • Protection System
    • Explosion relief valve
  • Special Tests / Reports
    • Neutral grounding connection
    • PGS test report @ 0.80 power factor
    • PGS test report @ 1.0 power factor
    • IBC seismic certifications
    • Neutral ground-LV
  • Starting / Charging Systems
    • 20 Amp battery charger
    • Jacket water heaters
    • Oversize battery set
    • 10 Amp battery chargers
    • Ether starting aid
    • 24 Volt dual electric starting motor
  • General
    • Engine barring group
    • Engine barring group
  • Control System
    • Controller: [ ] EMCP 4.2 [ ] EMCP 4.3 [ ] EMCP 4.4
    • Local annunciator module: [ ] NFPA 110 [ ] Custom