Your Rental Location
  • Request A Quote

3406C Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Videos not available for this product.

360 View not available for this product.

SPECIFICATION SUMMARY
  • Bore 5.4 in
  • Displacement 893.39 in3
  • Stroke 6.5 in
  • Aspiration TA

PRICE (USD)
Call 440-838-7348 for rate information

Engine Specifications

  • Bore
    5.4 in
  • Displacement
    893.39 in3
  • Stroke
    6.5 in
  • Aspiration
    TA
  • Fuel System
    P&L
  • Engine Model
    3406C TA, I-6, 4-Stroke Water-Cooled Diesel
  • Compression Ratio
    14.5:1
  • Governor Type
    Hydra-mechanical
  • Aspiration
    TA
  • Fuel System
    P&L
  • Bore
    5.4 in
  • Displacement
    893.39 inĀ³
  • Stroke
    6.5 in
  • Fuel System
    6.5 in

Generator Set Specifications

  • Minimum Rating
    275 kVA
  • Maximum Rating
    400 kVA
  • Voltage
    220 to 480 Volts
  • Frequency
    50 Hz
  • Speed
    1500 rpm
  • Emissions/Fuel Strategy
    Low Fuel Consumption

Generator

EMCP Control Panel

Design Criteria

UL 2200 / CSA - Optional

Single-Source Supplier

World Wide Product Support

Weight

Dimensions

Standard Equipment:

  • Air Inlet
    • Air Cleaner
  • Cooling
    • Package mounted radiator
  • Exhaust
    • Exhaust flange outlet
  • Fuel
    • Fuel priming pump
    • Primary fuel filter with integral water separator
    • Secondary fuel filter
  • Generator
    • IP23 Protection
    • Matched to the performance and output characteristics of Cat engines
    • Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
  • Power Termination
    • Bus Bar
  • Control Panel
    • EMCP 4 Genset Controller
  • Mounting
    • Rubber vibration isolators
  • Starting/charging
    • 24 volt starting motor
    • Batteries
  • General
    • Paint - Caterpillar Yellow except rails and radiators gloss black

Optional Equipment:

  • Exhaust
    • Industrial, Residential, Critical Mufflers
  • Generator
    • Anti-condensation heater
    • Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
    • Oversize and premium generators
  • Power Termination
    • Circuit breakers, UL listed
    • Circuit breakers, IEC compliant
  • Control Panels
    • Load share module
    • Local & remote annunciator modules
    • Digital I/O module
    • EMCP (4.2) (4.3) (4.4)
    • Remote monitoring software
  • Starting/charging
    • Oversize batteries
    • Battery chargers
    • Jacket water heater
    • Charging alternator
    • Heavy-duty starting system
  • General
    • CSA Certification
    • Narrow, Wide or Skid Base
    • Sound attenuated, weather protective or high ambient weather protective enclosure
    • Single or dual wall sub-base fuel tanks
    • The following options are based on regional and product configuration:
    • Automatic transfer switches (ATS)
    • Single or dual wall integral fuel tanks
    • Integral & sub-base UL listed dual wall fuel tanks
    • UL 2200 package
    • EU Certificate of Conformance (CE)
    • EEC Declaration of Conformity
    • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007