ATC-100 CONTROLLER

The ATC-100 is a comprehensive and multifunctional microprocessor-based ATS controller. It is a compact and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels.The ATC provides both fixed and jumper-selectable settings to allow for a range of applications. It operates from all system voltages between 120 and 480 Vac, single-phase and three phase at 50 or 60 Hz. The ATC-100 monitors the condition of the three-phase line to line voltage and the frequency of both the utility and generator power sources. It can also be set up for single-phase operation. The ATC-100 provides the necessary intelligence to ensure that the transfer switch operates properly through a series of selectable sensing and timing functions.

Videos not available for this product.

360 View not available for this product.

SPECIFICATION SUMMARY
  • Rating Range 120 to 480V, single phase and three phase @ 50/60 Hz
  • Transfer Type Switch application dependent
  • Switch Type Switch application dependent
  • Input Control Voltage 95 to 145 Vac 50/60 Hz

PRICE (USD)
Call 440-838-7348 for rate information

Technical Summary

  • Rating Range
    120 to 480V, single phase and three phase @ 50/60 Hz
  • Transfer Type
    Switch application dependent
  • Switch Type
    Switch application dependent
  • Rating Range
    120 to 480V, single phase and three phase @ 50/60 Hz
  • Transfer Type
    Switch application dependent
  • Switch Type
    Switch application dependent

ATC Controller Specifications

  • Input Control Voltage
    95 to 145 Vac 50/60 Hz
  • Voltage Measurements of Utility
    VAB generator VAB
    VBC generator VBC
    VCA generator VCA
  • Voltage Measurement Range
    0 to 575 Vac rms (50/60 Hz)
  • Voltage Measurement Accuracy
    ± 1% of full scale
  • Frequency Measurements Of
    Generator
  • Frequency Measurement Range
    40 Hz to 70 Hz
  • Frequency Measurement Accuracy
    ±0.3 Hz over the measurement range
  • Undervoltage Dropout
    80% of the nominal system voltage
  • Undervoltage Pickup
    90% of the nominal system voltage
  • Underfrequency Dropout Range
    90% of the nominal system frequency
  • Underfrequency Pickup Range
    95% of the nominal system frequency
  • Overfrequency Dropout Range
    115% of the nominal system frequency
  • Overfrequency Pickup Range
    110% of the nominal system frequency
  • Operating Temperature Range
    –20 to +70°C (–4 to +158°F)
  • Storage Temperature Range
    –30 to +85°C (–22 to +185°F)
  • Operating Humidity
    0 to 95% relative humidity (noncondensing)
  • Operating Environment
    Resistant to ammonia, methane, nitrogen, hydrogen and hydrocarbons
  • Generator Start Relay
    5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load
  • K1, K2 Relays

    10A, 1–3 hp @ 250 Vac

    10A@30 Vdc
  • Applicable Testing
    UL-recognized component
    UL 1008, UL 991 Environmental IEC 61000-4-2, 61000-4-3, 61000-4-4,
  • Applicable Testing Continued
    61000-4-5, 61000-4-6, 61000-4-11
    CISPR 11, Class B
    FCC Part 15, Class B
    CSS 22.2-178
  • Enclosure Compatibility
    NEMA 1, NEMA 3R and NEMA 12
    UV-resistant ATC-100 faceplate

Performance Features

  • Source 1 sensing:
    • Undervoltage / underfrequency
    • Overfrequency
  • Source 2 sensing:
    • Undervoltage / Overfrequency
  • Controller settings via jumpers located at the rear of the unit
  • Mimic diagram with source available and connected LED indication
  • System test pushbutton
  • Plant Exerciser - Selectable day, off, 7, 14 or 28 day intervals with fixed 15 minute run time
  • Monitor utility and generator power source voltages and generator power source frequency
  • Provides undervoltage protection of the utility and generator power sources
  • Provides underfrequency and overfrequency protection of the generator power source
  • Permits easy customer setup
  • Permits system testing
  • In-phase transition