60 Ton Air Conditioning Rental
Air conditioning units are self-contained and provide conditioned air for outdoor rental applications. Units are sound attenuated and are equipped with twin-scroll compressors. Units feature rental-friendly controls to meet the needs of the non-technical operator. Units are designed under industry guidelines and third-party safety and quality standards.
Videos not available for this product.
360 View not available for this product.
SPECIFICATION SUMMARY
- L X W X H: 11’7” x 8’ x 8’4”
- Shipping Weight: 8,400 lbs.
- Power Supply: 460 Volt / 3 Phase / 60 HZ with ground
- Entering Air Temp (Dry Bulb/Wet Bulb): 80.0 / 67.0°F
General
-
L X W X H:11’7” x 8’ x 8’4”
-
Shipping Weight:8,400 lbs.
-
Power Supply:460 Volt / 3 Phase / 60 HZ with ground
-
Entering Air Temp (Dry Bulb/Wet Bulb):80.0 / 67.0°F
-
Leaving air temp (dry bulb/wet bulb):52.6 / 51.0°F
-
Coil Construction:Cooper tube / Aluminum fins
-
Rows:8
-
Fins per inch:12
-
Filter (reusable):2 Piece Caged Media
-
Duct connections (8):19.2”
-
Cooling load:160 amps
-
Heating load:200 amps
-
Minimum circuit ampacity (cooling only):220 amps
-
Recommended Fuse / Circuit Breaker Rating:250 amps
-
Outside air damper:Manual
-
Space temperature control:Standard
-
Discharge air temperature control:Standard (4 x 20” Supply Air Duct)
-
Return air temperature control:Standard (4 x 20” Return Air Duct)
-
Design air flow:14,500 cfm @ 2 in wg
-
Maximum air flow:23,000 cfm @ 3 in wg
-
Design total static pressure:7 in. wg
-
Fan type:Reverse incline belt driven
-
Fan control:VFD
-
Motor power / speed:30 hp / 1725 rpm
-
Coil construction:Cooper tube / Aluminum fins
-
Compressor Type:Twin Scrolls
-
Crankcase Heat:140 watts
-
Refrigerant:R-410A
Electrical Data
Cooling Load: 160 amps
Heating Load: 200 amps
Minimum Circuit Ampacity (cooling only): 220 amps
Recommended Fuse/Curcuit Breaker Rating: 250 amps
System Control
Outside Air Damper: Manual
Space Temperature Control: Standard
Discharge Air Temperature Control: Standard (4 x 20 in. Supply Air Duct)
Return Air Temperature Control: Standard (4 x 20 in. Return Air Duct)
Fan Data
Design Air Flow: 14,500 cfm @ in wg
Maximum Air Flow: 23,000 cfm @ 3 in wg
Design Total Static Pressure: 7 in wg
Fan Type: Reverse incline belt driven
Fan Control: VFD
Motor Power/Speed: 30 hp / 1725 rpm
Cooling Data
Design Capacity: 75 tons
Entering Air Temp (dry bulb/wet bulb): 80/67.0 °F
Leaving Air Temp (dry bulb/wet bulb): 52.6/51.0 °F
Coil Construction: Copper Tube/Aluminum fins
Rows: 8
Fins Per Inch: 12
Heating Data
Type: Electric
Capacity: 130 kw
Heating: 444 MBH
Compressor Data
Type: Twin Scrolls
Crankcase Heat: 140 watts
Refrigerant: R-410A
Applications
Industrial and Commercial Spaces
Hospitals and Universities
Turbine and Motor Cooling
New Construction and Dehumidification
Warehouse Facilities
Temporary Job Sites
Manufacturing Facilities
Outdoor Events and Tents
Restoration
Temperature
Temperature Input: 67° to 80°F
Temperature Output: 51° to 52.6°F
Rental Advantages
Savings: Rentals let you get the performance you need without budgeting a purchase.
Flexibility: Flexible rental agreements let you keep your AC unit for as long as you need it.
Selection: The selection we offer makes it simple to get a unit that meets your demands.
Ease: We provide you with delivery, installation, startup, and product training, with 24/7 service and support.